title: Sentry PDU Devices: Outlet Power
|
||||
agents: snmp
|
||||
catalog: hw/power/servertech
|
||||
license: Proprietary
|
||||
distribution: Spearhead Systems SRL
|
||||
description:
|
||||
This check monitors the power of outlets in a Sentry PDU Device.
|
||||
Without configuration the status will always be OK, except when an infeed is
|
||||
returning no data.
|
||||
You are able to set warn/crit levels, such that the status may change to
|
||||
WARN or CRIT dependent on the levels.
|
||||
|
||||
item:
|
||||
The items are named "Outlet" with following socket ID and names.
|
||||
|
||||
inventory:
|
||||
One service per socket.
|
@ -0,0 +1,175 @@
|
||||
#!/usr/bin/env python
|
||||
#
|
||||
# Copyright 2024 Spearhead Systems SRL
|
||||
#
|
||||
# Docs for this system:
|
||||
# https://cdn10.servertech.com/assets/documents/documents/135/original/manual_CDU_Y-30932L.pdf
|
||||
# https://cdn10.servertech.com/assets/documents/documents/793/original/Sentry3.mib
|
||||
|
||||
from itertools import chain
|
||||
|
||||
|
||||
# A note about MAX_SOCKETS:
|
||||
#
|
||||
# According to the MIB, MAX_SOCKETS should be 64. However, since CheckMK 1.6
|
||||
# doesn't appear to have something like 2.*'s SNMPTree functionality, we
|
||||
# brute-force by explicitly querying every possible socket. Unfortunately,
|
||||
# this means querying ~3K OIDs. In practice, the data received from the customer
|
||||
# shows that they only have two or four sockets per infeed, so I've set the
|
||||
# MAX_SOCKETS here to 16, which cuts the queried OIDs to 800. Using MAX_SOCKETS
|
||||
# of 4 would still satisfy the customer's current needs, but leaves no leeway
|
||||
# if the get more sockets in an infeed.
|
||||
MAX_TOWERS = 4
|
||||
MAX_INFEEDS = 4
|
||||
MAX_SOCKETS = 16 # XXX
|
||||
|
||||
TOWER_ARR_SIZE = MAX_TOWERS
|
||||
INFEED_ARR_SIZE = MAX_TOWERS * MAX_INFEEDS
|
||||
SOCKET_ARR_SIZE = MAX_TOWERS * MAX_INFEEDS * MAX_SOCKETS
|
||||
|
||||
TOWER_NUM_OFFSET = 0
|
||||
INFEED_NUM_OFFSET = TOWER_NUM_OFFSET + 1
|
||||
INFEED_ID_OFFSET = INFEED_NUM_OFFSET + TOWER_ARR_SIZE
|
||||
INFEED_VOLT_OFFSET = INFEED_ID_OFFSET + INFEED_ARR_SIZE
|
||||
SOCKET_NUM_OFFSET = INFEED_VOLT_OFFSET + INFEED_ARR_SIZE
|
||||
SOCKET_ID_OFFSET = SOCKET_NUM_OFFSET + INFEED_ARR_SIZE
|
||||
SOCKET_NAME_OFFSET = SOCKET_ID_OFFSET + SOCKET_ARR_SIZE
|
||||
SOCKET_LOAD_OFFSET = SOCKET_NAME_OFFSET + SOCKET_ARR_SIZE
|
||||
|
||||
|
||||
def parse_sentry_pdu(info):
|
||||
outlets_info = {}
|
||||
results = info[0]
|
||||
num_towers = int(results[TOWER_NUM_OFFSET])
|
||||
|
||||
for tower_id in range(num_towers):
|
||||
num_infeeds = int(results[INFEED_NUM_OFFSET + tower_id])
|
||||
|
||||
for infeed_id in range(num_infeeds):
|
||||
infeed_idx = tower_id * MAX_TOWERS + infeed_id
|
||||
|
||||
infeed_sid = results[INFEED_ID_OFFSET + infeed_idx]
|
||||
infeed_voltage = float(results[INFEED_VOLT_OFFSET + infeed_idx]) / 10
|
||||
num_outlets = int(results[SOCKET_NUM_OFFSET + infeed_idx])
|
||||
|
||||
for outlet_id in range(num_outlets):
|
||||
outlet_idx = MAX_INFEEDS * MAX_SOCKETS * tower_id + MAX_SOCKETS * infeed_id + outlet_id
|
||||
outlet_sid = results[SOCKET_ID_OFFSET + outlet_idx]
|
||||
outlet_name = results[SOCKET_NAME_OFFSET + outlet_idx]
|
||||
outlet_load = float(results[SOCKET_LOAD_OFFSET + outlet_idx]) / 100
|
||||
|
||||
outlet_key = '%s.%s.%s' % (tower_id, infeed_id, outlet_id)
|
||||
outlets_info[outlet_key] = {
|
||||
'infeed_id': infeed_sid,
|
||||
'infeed_voltage': infeed_voltage,
|
||||
'outlet_id': outlet_sid,
|
||||
'outlet_name': outlet_name,
|
||||
'outlet_load': outlet_load
|
||||
}
|
||||
|
||||
return outlets_info
|
||||
|
||||
|
||||
def check_sentry_pdu(item, params, parsed):
|
||||
id = params['id']
|
||||
outlet = parsed.get(id)
|
||||
|
||||
if outlet is None:
|
||||
return (3, 'item not found in snmp data')
|
||||
|
||||
voltage = outlet['infeed_voltage']
|
||||
amps = outlet['outlet_load']
|
||||
|
||||
if voltage < 0:
|
||||
return (1, 'Infeed voltage unavailable')
|
||||
elif amps < 0:
|
||||
return (1, 'Outlet load unavailable')
|
||||
|
||||
power = voltage * amps
|
||||
state = 0
|
||||
|
||||
crit_watts_above = params.get('crit_watts_above')
|
||||
warn_watts_above = params.get('warn_watts_above')
|
||||
warn_watts_below = params.get('warn_watts_below')
|
||||
crit_watts_below = params.get('crit_watts_below')
|
||||
|
||||
if crit_watts_above and crit_watts_above < power:
|
||||
state = 2
|
||||
elif crit_watts_below and crit_watts_below > power:
|
||||
state = 2
|
||||
elif warn_watts_above and warn_watts_above < power:
|
||||
state = 1
|
||||
elif warn_watts_below and warn_watts_below > power:
|
||||
state = 1
|
||||
|
||||
return (state, '%.1f watts' % power)
|
||||
|
||||
|
||||
|
||||
def inventory_sentry_pdu(parsed):
|
||||
items = []
|
||||
|
||||
for id, outlet in parsed.items():
|
||||
name = '%s %s [infeed %s] power' % (
|
||||
outlet['outlet_id'],
|
||||
outlet['outlet_name'],
|
||||
outlet['infeed_id'])
|
||||
items.append((name, { 'id': id }))
|
||||
|
||||
return items
|
||||
|
||||
|
||||
check_info['sentry_pdu_outlets_power'] = {
|
||||
'parse_function': parse_sentry_pdu,
|
||||
'check_function': check_sentry_pdu,
|
||||
'inventory_function': inventory_sentry_pdu,
|
||||
'service_description': 'Outlet %s',
|
||||
'group': 'sentry_pdu_outlets_power',
|
||||
'snmp_info': (
|
||||
'.1.3.6.1.4.1.1718.3',
|
||||
# In CheckMK 2.* there is SMPTree, but 1.6 doesn't seem to have that.
|
||||
# Therefore we resort to this sledge-hammer approach to get the
|
||||
# information we need. It's... not ideal.
|
||||
list(chain(
|
||||
# Number of towers
|
||||
['1.4.0'],
|
||||
|
||||
# Number of infeeds
|
||||
# .1.3.6.1.4.1.1718.3.2.1.1.5.<tower #>
|
||||
['2.1.1.5.%s' % (x) for x in range(1, MAX_TOWERS+1)],
|
||||
|
||||
# Infeed IDs:
|
||||
# .1.3.6.1.4.1.1718.3.2.2.1.2.<tower #>.<infeed #>
|
||||
['2.2.1.2.%s.%s' % (x, y) for x in range(1, MAX_TOWERS+1)
|
||||
for y in range(1, MAX_INFEEDS+1)],
|
||||
|
||||
# Infeed voltage:
|
||||
# .1.3.6.1.4.1.1718.3.2.2.1.11.<tower #>.<infeed #>
|
||||
['2.2.1.11.%s.%s' % (x, y) for x in range(1, MAX_TOWERS+1)
|
||||
for y in range(1, MAX_INFEEDS+1)],
|
||||
|
||||
# Number of outlets
|
||||
# .1.3.6.1.4.1.1718.3.2.2.1.9.<tower #>.<infeed #>
|
||||
['2.2.1.9.%s.%s' % (x, y) for x in range(1, MAX_TOWERS+1)
|
||||
for y in range(1, MAX_INFEEDS+1)],
|
||||
|
||||
# Outlet IDs:
|
||||
# .1.3.6.1.4.1.1718.3.2.3.1.2.<tower #>.<infeed #>.<outlet #>
|
||||
['2.3.1.2.%s.%s.%s' % (x, y, z) for x in range(1, MAX_TOWERS+1)
|
||||
for y in range(1, MAX_INFEEDS+1)
|
||||
for z in range(1, MAX_SOCKETS+1)],
|
||||
|
||||
# Outlet names:
|
||||
# .1.3.6.1.4.1.1718.3.2.3.1.3.<tower #>.<infeed #>.<outlet #>
|
||||
['2.3.1.3.%s.%s.%s' % (x, y, z) for x in range(1, MAX_TOWERS+1)
|
||||
for y in range(1, MAX_INFEEDS+1)
|
||||
for z in range(1, MAX_SOCKETS+1)],
|
||||
|
||||
# Outlet load:
|
||||
# .1.3.6.1.4.1.1718.3.2.3.1.7.<tower #>.<infeed #>.<outlet #>
|
||||
['2.3.1.7.%s.%s.%s' % (x, y, z) for x in range(1, MAX_TOWERS+1)
|
||||
for y in range(1, MAX_INFEEDS+1)
|
||||
for z in range(1, MAX_SOCKETS+1)],
|
||||
))),
|
||||
'snmp_scan_function': lambda oid: 'Sentry Switched -48 VDC' in oid('.1.3.6.1.2.1.1.1.0')
|
||||
}
|
@ -0,0 +1,88 @@
|
||||
#!/usr/bin/env python3
|
||||
#
|
||||
# Copyright 2024 Spearhead Systems SRL
|
||||
|
||||
from cmk.gui.i18n import _
|
||||
from cmk.gui.plugins.wato import (
|
||||
rulespec_registry,
|
||||
CheckParameterRulespecWithItem,
|
||||
RulespecGroupCheckParametersEnvironment,
|
||||
)
|
||||
from cmk.gui.valuespec import (
|
||||
Dictionary,
|
||||
Integer,
|
||||
)
|
||||
|
||||
|
||||
def _valuespec_outlets_power_check():
|
||||
return Dictionary(
|
||||
optional_keys=[
|
||||
'crit_watts_above',
|
||||
'warn_watts_above',
|
||||
'warn_watts_below',
|
||||
'crit_watts_below'
|
||||
],
|
||||
elements=[
|
||||
(
|
||||
'crit_watts_above',
|
||||
Integer(
|
||||
minvalue=0,
|
||||
title=_('Crit when above power'),
|
||||
unit=_('Watts'),
|
||||
help=_(
|
||||
'If the Wattage of an outlet goes above this number, enter a critical state.'
|
||||
),
|
||||
),
|
||||
),
|
||||
(
|
||||
'warn_watts_above',
|
||||
Integer(
|
||||
minvalue=0,
|
||||
title=_('Warn when above power'),
|
||||
unit=_('Watts'),
|
||||
help=_(
|
||||
'If the Wattage of an outlet goes above this number, enter a warning state.'
|
||||
),
|
||||
),
|
||||
),
|
||||
(
|
||||
'warn_watts_below',
|
||||
Integer(
|
||||
minvalue=0,
|
||||
title=_('Warn when below power'),
|
||||
unit=_('Watts'),
|
||||
help=_(
|
||||
'If the Wattage of an outlet goes below this number, enter a warning state.'
|
||||
),
|
||||
),
|
||||
),
|
||||
(
|
||||
'crit_watts_below',
|
||||
Integer(
|
||||
minvalue=0,
|
||||
title=_('Crit when below power'),
|
||||
unit=_('Watts'),
|
||||
help=_(
|
||||
'If the Wattage of an outlet goes below this number, enter a critical state.'
|
||||
),
|
||||
),
|
||||
),
|
||||
],
|
||||
)
|
||||
|
||||
|
||||
def _item_spec_outlets_power_check():
|
||||
return TextAscii(title=_('Socket Name'),
|
||||
help=_('The name of the socket'))
|
||||
|
||||
|
||||
rulespec_registry.register(
|
||||
CheckParameterRulespecWithItem(
|
||||
check_group_name='sentry_pdu_outlets_power',
|
||||
group=RulespecGroupCheckParametersEnvironment,
|
||||
match_type='dict',
|
||||
item_spec=_item_spec_outlets_power_check,
|
||||
parameter_valuespec=_valuespec_outlets_power_check,
|
||||
title=lambda: _('Sentry PDU Outlets Power Checks'),
|
||||
)
|
||||
)
|
@ -0,0 +1,165 @@
|
||||
#!/usr/bin/env python3
|
||||
#
|
||||
# Copyright 2024 Spearhead Systems SRL
|
||||
#
|
||||
# Docs for this system:
|
||||
# https://cdn10.servertech.com/assets/documents/documents/135/original/manual_CDU_Y-30932L.pdf
|
||||
# https://cdn10.servertech.com/assets/documents/documents/793/original/Sentry3.mib
|
||||
|
||||
from cmk.base.plugins.agent_based.agent_based_api.v1 import (
|
||||
register,
|
||||
Service,
|
||||
Result,
|
||||
State,
|
||||
SNMPTree,
|
||||
contains,
|
||||
OIDEnd,
|
||||
)
|
||||
|
||||
|
||||
def extract_outlet(tower_id, infeed_id, outlet_id, data):
|
||||
return next(filter(lambda x: x[0] == f'{tower_id+1}.{infeed_id+1}.{outlet_id+1}', data))[1]
|
||||
|
||||
|
||||
# SNMP parsing function
|
||||
def parse_sentry_pdu(string_table):
|
||||
outlets_info = {}
|
||||
num_towers = int(string_table[0][0][0])
|
||||
|
||||
for tower_id in range(num_towers):
|
||||
num_infeeds = int(string_table[1][0][tower_id])
|
||||
|
||||
for infeed_id in range(num_infeeds):
|
||||
infeed_sid = string_table[2][infeed_id][tower_id]
|
||||
infeed_voltage = float(string_table[3][infeed_id][tower_id]) / 10
|
||||
num_outlets = int(string_table[4][infeed_id][tower_id])
|
||||
|
||||
for outlet_id in range(num_outlets):
|
||||
outlet_sid = extract_outlet(tower_id, infeed_id, outlet_id, string_table[5])
|
||||
outlet_name = extract_outlet(tower_id, infeed_id, outlet_id, string_table[6])
|
||||
outlet_load = float(extract_outlet(tower_id, infeed_id, outlet_id, string_table[7])) / 100
|
||||
|
||||
outlets_info[f'{tower_id}.{infeed_id}.{outlet_id}'] = {
|
||||
'infeed_id': infeed_sid,
|
||||
'infeed_voltage': infeed_voltage,
|
||||
'outlet_id': outlet_sid,
|
||||
'outlet_name': outlet_name,
|
||||
'outlet_load': outlet_load
|
||||
}
|
||||
|
||||
return outlets_info
|
||||
|
||||
|
||||
# Inventory function, returning inventory based upon SNMP parsed result above
|
||||
def discovery_sentry_pdu(section):
|
||||
for key, outlet in section.items():
|
||||
name = f'{outlet["outlet_id"]} {outlet["outlet_name"]} (infeed {outlet["infeed_id"]}) power'
|
||||
yield Service(item=name, parameters={ 'id': key })
|
||||
|
||||
|
||||
# Check function, returning warn/crit based upon SNMP parsed result above
|
||||
def check_sentry_pdu(item, params, section):
|
||||
outlet = section.get(params['id'])
|
||||
if outlet is None:
|
||||
return
|
||||
|
||||
voltage = outlet['infeed_voltage']
|
||||
amps = outlet['outlet_load']
|
||||
|
||||
if voltage < 0:
|
||||
yield Result(state=State.WARN, summary='Infeed voltage unavailable')
|
||||
return
|
||||
elif amps < 0:
|
||||
yield Result(state=State.WARN, summary='Outlet load unavailable')
|
||||
return
|
||||
|
||||
power = voltage * amps
|
||||
state = State.OK
|
||||
|
||||
crit_watts_above = params.get('crit_watts_above')
|
||||
warn_watts_above = params.get('warn_watts_above')
|
||||
warn_watts_below = params.get('warn_watts_below')
|
||||
crit_watts_below = params.get('crit_watts_below')
|
||||
|
||||
if crit_watts_above and crit_watts_above < power:
|
||||
state = State.CRIT
|
||||
elif crit_watts_below and crit_watts_below > power:
|
||||
state = State.CRIT
|
||||
elif warn_watts_above and warn_watts_above < power:
|
||||
state = State.WARN
|
||||
elif warn_watts_below and warn_watts_below > power:
|
||||
state = State.WARN
|
||||
|
||||
yield Result(state=state, summary=f'{power:.1f} watts')
|
||||
|
||||
|
||||
register.snmp_section(
|
||||
name='sentry_pdu_outlets_power',
|
||||
parse_function=parse_sentry_pdu,
|
||||
fetch=[
|
||||
# Number of towers (integer from 0 to 4)
|
||||
SNMPTree(
|
||||
base='.1.3.6.1.4.1.1718.3.1.4',
|
||||
oids=['0']
|
||||
),
|
||||
|
||||
# Number of infeeds (integer from 0 to 4):
|
||||
# .1.3.6.1.4.1.1718.3.2.1.1.5.<tower #>
|
||||
SNMPTree(
|
||||
base='.1.3.6.1.4.1.1718.3.2.1.1.5',
|
||||
oids=['1', '2', '3', '4'],
|
||||
),
|
||||
|
||||
# Infeed IDs:
|
||||
# .1.3.6.1.4.1.1718.3.2.2.1.2.<tower #>.<infeed #>
|
||||
SNMPTree(
|
||||
base='.1.3.6.1.4.1.1718.3.2.2.1.2',
|
||||
oids=['1', '2', '3', '4'],
|
||||
),
|
||||
|
||||
# Infeed voltage:
|
||||
# .1.3.6.1.4.1.1718.3.2.2.1.11.<tower #>.<infeed #>
|
||||
SNMPTree(
|
||||
base='.1.3.6.1.4.1.1718.3.2.2.1.11',
|
||||
oids=['1', '2', '3', '4'],
|
||||
),
|
||||
|
||||
# Number of outlets (integer from 0 to 64):
|
||||
# .1.3.6.1.4.1.1718.3.2.2.1.9.<tower #>.<infeed #>
|
||||
SNMPTree(
|
||||
base='.1.3.6.1.4.1.1718.3.2.2.1.9',
|
||||
oids=['1', '2', '3', '4'],
|
||||
),
|
||||
|
||||
# Outlet IDs:
|
||||
# .1.3.6.1.4.1.1718.3.2.3.1.2.<tower #>.<infeed #>.<outlet #>
|
||||
SNMPTree(
|
||||
base='.1.3.6.1.4.1.1718.3.2.3.1',
|
||||
oids=[OIDEnd(), '2'],
|
||||
),
|
||||
|
||||
# Outlet names:
|
||||
# .1.3.6.1.4.1.1718.3.2.3.1.3.<tower #>.<infeed #>.<outlet #>
|
||||
SNMPTree(
|
||||
base='.1.3.6.1.4.1.1718.3.2.3.1',
|
||||
oids=[OIDEnd(), '3'],
|
||||
),
|
||||
|
||||
# Outlet load:
|
||||
# .1.3.6.1.4.1.1718.3.2.3.1.7.<tower #>.<infeed #>.<outlet #>
|
||||
SNMPTree(
|
||||
base='.1.3.6.1.4.1.1718.3.2.3.1',
|
||||
oids=[OIDEnd(), '7']
|
||||
),
|
||||
],
|
||||
detect=contains('.1.3.6.1.2.1.1.1.0', 'Sentry Switched -48 VDC'),
|
||||
)
|
||||
|
||||
register.check_plugin(
|
||||
name='sentry_pdu_outlets_power',
|
||||
service_name='Outlet %s',
|
||||
discovery_function=discovery_sentry_pdu,
|
||||
check_function=check_sentry_pdu,
|
||||
check_default_parameters={},
|
||||
check_ruleset_name='sentry_pdu_outlets_power',
|
||||
)
|
@ -0,0 +1,81 @@
|
||||
#!/usr/bin/env python3
|
||||
#
|
||||
# Copyright 2024 Spearhead Systems SRL
|
||||
|
||||
from cmk.gui.i18n import _
|
||||
from cmk.gui.plugins.wato.utils import (
|
||||
rulespec_registry,
|
||||
CheckParameterRulespecWithItem,
|
||||
RulespecGroupCheckParametersEnvironment,
|
||||
)
|
||||
from cmk.gui.valuespec import (
|
||||
Dictionary,
|
||||
Integer,
|
||||
)
|
||||
|
||||
|
||||
def _valuespec_agents_sentry_pdu_outlets_power_check():
|
||||
return Dictionary(
|
||||
title=_('Sentry PDU Outlets Power Checks'),
|
||||
optional_keys=[
|
||||
'crit_watts_above',
|
||||
'warn_watts_above',
|
||||
'warn_watts_below',
|
||||
'crit_watts_below'
|
||||
],
|
||||
elements=[
|
||||
(
|
||||
'crit_watts_above',
|
||||
Integer(
|
||||
minvalue=0,
|
||||
title=_('Crit when above power'),
|
||||
unit=_('Watts'),
|
||||
help=_(
|
||||
'If the Wattage of an outlet goes above this number, enter a critical state.'
|
||||
),
|
||||
),
|
||||
),
|
||||
(
|
||||
'warn_watts_above',
|
||||
Integer(
|
||||
minvalue=0,
|
||||
title=_('Warn when above power'),
|
||||
unit=_('Watts'),
|
||||
help=_(
|
||||
'If the Wattage of an outlet goes above this number, enter a warning state.'
|
||||
),
|
||||
),
|
||||
),
|
||||
(
|
||||
'warn_watts_below',
|
||||
Integer(
|
||||
minvalue=0,
|
||||
title=_('Warn when below power'),
|
||||
unit=_('Watts'),
|
||||
help=_(
|
||||
'If the Wattage of an outlet goes below this number, enter a warning state.'
|
||||
),
|
||||
),
|
||||
),
|
||||
(
|
||||
'crit_watts_below',
|
||||
Integer(
|
||||
minvalue=0,
|
||||
title=_('Crit when below power'),
|
||||
unit=_('Watts'),
|
||||
help=_(
|
||||
'If the Wattage of an outlet goes below this number, enter a critical state.'
|
||||
),
|
||||
),
|
||||
),
|
||||
],
|
||||
)
|
||||
|
||||
rulespec_registry.register(
|
||||
CheckParameterRulespecWithItem(
|
||||
check_group_name='sentry_pdu_outlets_power',
|
||||
group=RulespecGroupCheckParametersEnvironment,
|
||||
match_type='dict',
|
||||
parameter_valuespec=_valuespec_agents_sentry_pdu_outlets_power_check,
|
||||
)
|
||||
)
|
Loading…
Reference in New Issue
Block a user